Fire Door Locks Chelsea Fire Exit and Flat Entrance Doors
We repair and replace the fire door lock on fire exits and flat entrance doors across Chelsea, fitting panic bars to BS EN 1125, push pads to BS EN 179 and mortice locks suitable for fire doors, usually reaching SW3 and SW10 within 30 minutes. Because the hardware depends on the door's rating and who uses the route, fire door work is priced on the phone before we set off; a closer adjusted alongside it is £40 to £75. There is no call out fee. We are locksmiths, not fire risk assessors, and we fit to the requirements of your assessment.
- DBS checked locksmith
- Public liability insured
- Over 5 years working in Chelsea
- Price agreed before work
- No call out fee
Why a fire door lock is not an ordinary lock
A fire door is a tested set of parts: the leaf, the frame, the hinges, the seals, the closer and the lock. If one part is swapped for something untested, the door may no longer hold fire and smoke back for the 30 or 60 minutes it was made for. Most doors you will meet in Chelsea are FD30 or FD30S, the S meaning it also carries smoke seals.
The lock matters because its case sits in a pocket cut into the door. That pocket weakens the leaf, so the lock fitted must be one its maker states is suitable for fire doors of that rating, and the pocket is usually lined with intumescent material that swells in heat to fill the gap. A bigger lock case, an extra hole for a second lock, or a cylinder that leaves gaps around it can all undermine the door.
When we change a lock on a fire door we match the case size, keep or renew the intumescent packing, and avoid new cut outs wherever possible.
Flat entrance fire doors in blocks
In a purpose built or converted block, the front door of each flat is normally a fire door onto the communal stair. In England, the managing agent or freeholder of a residential building over 11 metres must make regular checks on flat entrance doors and on the communal fire doors, so faults found by those checks often lead to a call to us.
Typical faults on Chelsea flat doors:
- A closer removed or disconnected because the door felt heavy.
- A second lock added by a tenant with the intumescent strip cut around it.
- A non fire rated letter plate or spy viewer fitted after the door was installed.
- Gaps around the frame wider than the seals can close.
We replace the lock with a suitable one, refit or renew the self closer and fit fire rated letter plates and viewers where needed. Gaps in the frame or a damaged leaf may need a door specialist and we will tell the agent. For the rest of the communal hardware in these buildings, see our mansion block locksmith page.
Fire door lock and exit hardware prices
Fire door hardware is priced on the phone once we know the door rating and device, and related items follow our list with no call out fee.
| Job | Typical price |
|---|---|
| Panic bar, push pad or fire door lock Device or lock suited to the door, figure agreed before we travel | Priced on the phone |
| Door closer fitted or repaired Self closer adjusted or replaced so the door latches | £40 to £75 |
| Lock repair (stiff, jammed lock) Existing fire door lock eased or serviced | £35 to £60 |
| Door repair (timber or front door, frame, hinges) Hinges and hang corrected so the lock and seals line up | £50 to £120 |
| Break in repair and secure up Damaged door made lockable until a rated replacement is fitted | £75 to £175 |
Prices include parts and labour. The lower figure is a standard daytime job, the higher figure covers nights, weekends and high security parts. Your exact price is confirmed on the phone before we travel, with no call out fee. See the full Chelsea price list.
Panic bars and push pads on fire exits
A fire exit must open in one movement from inside without a key. The right device depends on who will be using the door in an emergency.
Panic bar, BS EN 1125
A horizontal bar across the door that releases when pushed anywhere along its length. Used where members of the public, who do not know the building, may need to escape: shops, restaurants, galleries.
Public escape routes
Push pad or lever, BS EN 179
A smaller pad or lever handle for routes used only by staff who know the building and the door. Common on office back stairs and staff areas.
Staff only routes
Outside access device
A lever or key operated unit on the outside of a panic exit, letting staff come back in while the inside stays free to open.
Only where your assessment allows it
On double fire exit doors, both leaves usually need devices and the door must close in the right order, with the leaf carrying the rebate shutting last. A selector fitted at the head does this, and we check it alongside the bars.
Fire door lock faults, causes and fixes
| Symptom | Likely cause | What we do |
|---|---|---|
| Panic bar pushed but door stays shut | Rods bent, bolts binding in the floor socket or head keep | Free and realign rods, clear the floor socket, adjust keeps |
| Exit door will not stay locked at night | Worn latch in the device or door dropped on its hinges | Reset the hang, repair or replace the device |
| Flat door will not latch on its own | Closer too weak or latch speed too slow | Adjust or replace the closer, check the latch meets the keep |
| Key turns stiffly in a fire rated lock | Door swelling or a worn cylinder | Ease the door, service or replace the lock with a suitable fire rated type |
| Door wedged open by staff | Heavy closer, deliveries, ventilation | Discuss an alarm linked hold open device with your assessor |
A wedge on a fire door is one of the most common faults. If people prop a door because it is hard to open, the fix is usually a correctly sized closer, covered on our door closer repair page, or a hold open device that releases when the alarm sounds.
Fire door repair: what we will not do
Honest limits
We will not fit a lock that is not suitable for fire doors onto a fire door, cut away intumescent seals to make a lock fit, disconnect a closer on a fire door, or put a key locked device on an escape route. If a customer asks for any of those, we explain why and offer an alternative.
We also do not certify doors or write fire risk assessments. Those come from a competent fire risk assessor, and in many blocks the managing agent will already have one. What we can do is fit the hardware the assessment calls for, record the make and model on the invoice and point out anything visibly wrong while we are there.
Where a fire door itself is damaged after a break in, our secure up service makes the door lockable that night, and the agent can then arrange a like for like rated replacement. For general timber door faults that are not fire rated, see door repair in Chelsea.
Fire door locks for shops, offices and landlords
On the King's Road and Fulham Road, rear fire exits from shops and restaurants are the usual job: a panic bar that has stopped working, or a door that staff cannot lock at closing time. In offices above shops, the stair door from each floor is a fire door, often with a push pad on the escape side. Landlords of HMOs and converted houses have fire doors to bedrooms and the kitchen, where a thumb turn lock that opens from inside without a key is often what the assessment asks for. See our landlord locksmith page for tenancy work.
For the broader picture of business security, read our commercial locksmith Chelsea page. If you want staff to use fobs on an exit door, our access control page explains fail safe locks and alarm links. All published prices are on our Chelsea locksmith price list, and our other trades are listed on the locksmith services page.
Common questions
Can I put any lock on a fire door?
No. The lock must be one its maker states is suitable for fire doors of that rating, its case must fit the existing pocket, and the intumescent packing must be kept. Adding extra locks with new cut outs can weaken the door.
What is the difference between a panic bar and a push pad?
A panic bar to BS EN 1125 runs across the door and is for routes the public may use. A push pad or lever to BS EN 179 is for staff who know the building. Your fire risk assessment says which applies.
Does a flat entrance door need a self closer?
In most blocks the flat front door is a fire door onto the common stair, and it needs a working self closer so it shuts on its own. Disconnecting it because the door is heavy is a common fault we are asked to fix.
Can you lock a fire exit at night?
A fire exit must open from inside without a key whenever people are in the building. When the premises are empty, some businesses add security measures, but only as your fire risk assessment allows. We will discuss options on the call.
Are you a fire door inspector?
No. We are locksmiths and do not certify or inspect doors. We fit and repair fire door locks, exit devices and closers to match your assessment, and we point out obvious faults so your agent or assessor can deal with them.
How much is fire door repair in London?
Lock and exit device work is priced on the phone once we know the door. A closer is £40 to £75 and a lock repair £35 to £60, with no call out fee. See our prices for the full list.
Related pages
Fire exit not opening or not locking?
Call 07520 643913 and tell us the door rating and device so we can price it before we set off.